TECO T-verter N2 Series - Manually Resettable, Non-Auto Resettable Faults

TECO T-verter N2 Series
83 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
62
OH-C
Over Heat during
Constant speed
1. Load is too high
2. Ambient temperature is
too high or ventilation is
poor
1. Investigate load condition
2. Select a larger HP T-verter
3. Lower ambient temperature or
improve ventilation
OH1
Braking resistor
overload
1. Decel. Time is too short
2. Frequent run/stop
operation
3. Load is too high
1. Prolong Decel. Time.
2. Prolong run/stop cycle
3. Set Fn_44 to xx0x and increase
resistance of braking resistor
Faults, which can be reset by manual operation, but cannot be auto reset
Fault Code Content Probable Cause What to do
- OC-
Over current
during stop mode
1.Detecting circuit failure
2. CT Signal cable Failure
1. Send T-verter back for repairing
OL1 Motor overload
1. Load is too high
2. Inappropriate V/F
pattern selection
3. Incorrect Fn_69, Fn_70
setting
1. Select a larger HP T-verter
2. Select optimum V/F pattern
3. Select correct Fn_69 & Fn_70
setting
OL2 T-verter overload
1. Load is too high
2. Inappropriate V/F
pattern selection
1. Select a larger HP T-verter
2. Select optimum V/F pattern
OL3 Over-torque
1. Load is too high
2. Inappropriate V/F pattern
selection
3. Fn_78, Fn_79 are set
too low
1. Select a larger HP T-verter
2. Select optimum V/F pattern
3. Select appropriate Fn_78 &
Fn_79 settings