Special Condition Indication
Fault Code Content Illustration
STP0 Zero speed stop
1. Fn_11 = 0 or 3, Fn_07 <0.1 Hz, and setting freq.<0.1 Hz;
Fn_11 = 1 or 23, Fn_07 <(Fn_06/100), and setting freq.
<0.1 Hz
STP1 Direct start disable
1. Power switched on while remote RUN switched on
(Fn_10)
Direct start is prohibited (Fn_16= xxx1). T-verter
can not be started and will display STP1.(Refer to Fn_16)
T-verter can be started directly when Fn_16 = xxx0
STP2
Emergency stop
command by
STOP key
1. Emergency stop via digital operator in remote control mode
(Fn_10 = 1) by pressing STOP key (Fn_48 = xx0x). Once
STOP key is pressed during operation, T-verter will stop
according to the setting of Fn_44 and display STP2. T-verter
will not restart until power is turned off and on again.
2. If the T-verter is under communications control and Fn_48 =
xx0x, Once STOP key is pressed, T-verter will stop according
to the setting of Fn_44 and display STP2. T-verter will not
restart until computer sends Stop command followed by a
RUN command
3. STOP key can not be used for emergency stop when
Fn_48=xx1x.
E.S.
Emergency stop
command by
remote control
1. Emergency stop via remote control mode (multi-function
input terminals), The T-verter will decelerate to stop and
display E.S.
b.b.
External
base-block
External abnormal signal base-blocks T-verter via multi-function
input terminals (please refer to Fn_56-60)