21
NT935 ETH
SYSTEM: Setting and Status
Address
LO
(10)
Data HI
Data LO
Note 1
Note 2
R: read
W:write
RW:
read/write
10
00
HFN (Fan test)
0=No test
1÷200h
RW
11
00
FCD
temperature
increment
0=No FCD
1÷30°/sec
RW
12
00
Voting
0=No Voting
1=YES
RW
13
00
CPU Setting
See Note
RW
14
00
CPU Error
See Note
R
15
00
Relays Status
See Note
R
16
00
420 mA channel
reference
channel for
4.20 mA
0=hot
1÷4= ch1÷4
5=scan
RW
Only for AD
version
17
00
Address
Modbus
address
1÷255
R
18
00
Bdr
Modbus baud
rate
0=2400
1=4800
2=9600
3=19200
4=38400
R
19
00
Parity
Modbus parity
bit
0=N-1 (1 stop)
1=Even
2=Odd
3= N-2 (2 stop)
R
20
00
FREE
See Note
R
TEMPERATURE FANs:
Address
LO
(10)
Data HI
Data LO
Note 1
Note 2
R: read
W:write
RW: read/write
21
2’compl. sign
Fan_1 ON
1°C ÷ 240°C
1°C ÷ 200°C (*)
RW
22
2’compl. sign
Fan_1 OFF
1° to÷ 240°
1°C ÷ 200°C (*)
RW
23
2’compl. sign
Fan_2 ON
1° to÷ 240°
1°C ÷ 200°C (*)
RW
24
2’compl. sign
Fan_2 OFF
1° to÷ 240°
1°C ÷ 200°C(*)
RW
(*) for version 40°C ÷ +200°C