EasyManuals Logo

TECSYSTEM NT935 ETH User Manual

TECSYSTEM NT935 ETH
33 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #6 background imageLoading...
Page #6 background image
6
NT935 ETH
TECHNICAL SPECIFICATIONS
NT935 ETH
POWER SUPPLY
Supply rated values
85-260 Vac-Vdc
50/60HZ
Vdc with reversible polarities
INPUTS
4 inputs for RTD sensors, Pt100 type with 3 wires (max section 1.5mm²)
Connections on removable terminal strips
Input channels protected against electromagnetic interference
Cable compensation for thermistors
500m (1mm²)
OUTPUTS
2 alarm relays (ALARM AND TRIP) SPDT
1 sensor or operating failure (FAULT) relay SPST
Output relays with 10A-250Vac-res COSФ=1 contacts.
2 ventilation management relays SPST FAN 1 AND FAN 2
Ethernet output 10Base T / 100Base-TX Modbus TCP slave.
DIMENSIONS
100x100 mm din43700-depth 131mm (terminal block included)
Hole 92 x 92 mm
TESTS AND PERFORMANCE
Construction in compliance with CE regulations
Protection from electrical interference EN 61000-4-4
Dielectric strength 1500 Vac for a min. between output relays and sensors, relays and power
supply, power supply and sensors
Accuracy ±1% vfs, ±1 digit
Ambient operating temperature from 20°C to +60°C
Humidity 90% non-condensing
Frontal film polycarbonate IP65