Setup – System Setup Menu
Description Range Access
SNOW/ICE SENSOR
Select if a Snow/Ice Sensor 090 or 094 "Inslab", or a Snow Sensor 095 "Aerial" is installed.
Conditions: Always available.
None,
In-slab, Aerial
Default = In-slab
Installer
SLAB SENSOR
Select if a Slab Sensor 072 or 073 is installed.
Conditions: Available when snow/ice sensor is set to None or Aerial.
Off or On
Default = Off
Installer
ECONOMELT
EconoMelt allows the user to mechanically remove snow then manually start the system
to melt the remaining thin snow layer or ice with an automatic stop when the sensor is dry.
Requires snow/ice sensor to be set to in-slab
Off or On
Default = Off
Installer
MAX MELT DAYS
Limit the amount of melting run time after snow is automatically detected by a Snow/Ice
Sensor 090 or 094, or a Snow Sensor 095.
Conditions: Always available.
Off, 0.5 to 7 days
Default = 3 days
Installer
OUTDOOR SENSOR
Select if the outdoor air temperature is measured by the control, by a tekmarNet system or
by the Internet weather service.
Conditions: Always available.
Control,
tekmarNet,
Internet
Default = Control
Installer
Setup – Boiler Setup Menu
Description Range Access
BOILER TYPE
Select the type of boiler operated by the control.
Enable = Boiler relay turns on the heat source.
Control = Call for heat to tekmarNet control.
Conditions: Available when the 671 is connected to a tekmarNet system.
Enable,
Control
Installer