10 Fire Control Panel MAG2/4 - User Manual
8. Operation instructions
8.1 Zone Enabling/ Disabling
Z To disable a zone:
• Press ENABLE/ DISABLE:
DISABLE/ ENABLE LED blinks.
The ZONE 1 yellow LED blinks if ZONE 1 is en-
abled and lights permanently if ZONE 1 is disabled.
Press TEST/ SCROLL, until
you reach the zone which has to
be disabled:
The respective zone yellow LED blinks.
• Press ENABLE/ DISABLE:
The yellow LED of the disabled zone lights up per-
manently.
• Press RESET: At this step the zone is disabled.
Z To enable a zone:
• Press ENABLE/ DISABLE:
DISABLE/ ENABLE LED blinks.
The ZONE 1 yellow LED blinks if ZONE 1 is en-
abled and lights permanently if ZONE 1 is disabled.
Press TEST/SCROLL, until you
reach the zone which has to en-
able:
The yellow LED of the disabled zone lights up per-
manently.
• Press ENABLE/ DISABLE: The yellow LED of the enabled zone blinks.
• Press RESET: At this step the zone is enabled.
8.2 Sounders Enabling/ Disabling
!
A sound signalization is activated at every Service Mode entering. The
signalization is off by pressing “SILENCE BUZZER button.
Z To disable the sounders:
• Press ENABLE/ DISABLE:
DISABLE/ ENABLE LED blinks.
The ZONE 1 yellow LED blinks if ZONE 1 is en-
abled and lights permanently if ZONE 1 is disabled.
Press TEST/ SCROLL, until
you reach the last zone in the
system:
The SOUNDER FAULT/DISABLE LED will start
blinking.
• Press ENABLE/ DISABLE:
The SOUNDER FAULT/DISABLE LED lights up
permanently.