4. The device will respond with activated indication and signalization depending on its type:
Device
Type
Signalization
Action
TD
Heat detector
LEDs
+
Sound
LEDs are flashing in orange
accompanied with short sound signals.
SD
Optical-smoke detector
MD
Combined detector
WSS
Sounder with strobe
LEDs are flashing accompanied with
short sound signals.
MCP
Manual call point
LED
The status LED is flashing in red.
MCP-DE
Manual call point
MIO
Input-output module
5. The module will exit automatically the finding procedure after 70-80 seconds. You can also stop
the procedure at any time with pressing CANCEL button.
6. Press CANCEL button again to exit from the menu for finding devices.
14. Settings parameters of wireless devices
In 4. DEVICE SETUP menu the installer can set some parameters of the devices and also to
perform Enabling/Disabling of their operation.
Enter in programming mode of the module. Scroll to menu 4. DEVICE SETUP and press ENTER
button. A list with present enrolled devices is shown on the screen with an order number and type
of the device. Scroll to a device and press ENTER button to access the settings.
The following table presents the available settings according the device type.
Setup Menu
MCP
SD
TD
MD
WSS
ENABLE/DISABLE
BUZZER
TONE
VOLUME
MODE
14.1 Menu for Enable/Disable of Device
In the menu the installer can perform Enabling/Disabling of the operation of a device. The
disabled devices do not send information about their status to the expander (network gateway)
module. The disabled devices will not react on alarm events. The menu is available for all Natron
series wireless devices.
To perform enabling/disabling, from the main menu scroll to 4. DEVICE SETUP and select a
device number with the arrow buttons. Press ENTER. Select menu 1. ENABLE/DISABLE and
press ENTER button. There are two setting, as the currently set is displayed on the screen. The
setting is changed with pressing up/down arrow buttons.
- ENABLED set by default. The device will report its current status to the module and
will react on alarm events. Its operation is enabled.
- DISABLED. The device will not report its current status or alarm events to the module.
Its operation is disabled.
Confirm the setting with ENTER button the exit of the menu is automatic.
ATTENTION: The disabling of sounders is not according the requirement of EN 54-2!