The meaning of the displayed messages is as follows:
Message
Type
Description
Fire Alarm
Alarm
The message is with the highest priority and is displayed in case
if fire alarm event activation of wireless fire detector or call
point.
Device Lost
Fault
There is no communication between the expander (network
gateway) module and a wireless device. The possible reasons
might be: no power supply of the device (absence or discharged
batteries), signal lost or jamming.
High Dust
Fault
The smoke chamber of a fire detector is dirty and must be
cleaned immediately.
Chamber Fault
Fault
There is a problem with the smoke chamber of a wireless device.
Tamper
Warning
Open tamper switch of a wireless detector or sounder the
device has been removed from its base.
Low Battery
Warning
The level of the power batteries is low. The batteries must be
changed in one month time period after this message is
displayed.
The message for the event is displayed always on the first row and on the second is displayed the
order number of the device in the module’s configuration and its type:
In the example above, after pressing a random button at the front panel, the fault message is
displayed at first place, because of its higher priority. Use the arrows to review if there are other
messages with lower priority.
The exit from the events’ reviewing mode is automatic after 2 minutes, if there is no button
pressed or other operation.
If currently there are no events, after pressing a random button, only NATRON text is displayed on
the screen.