SIMPO - BASIC INFORMATION
Page 7 of 48
Simpo Addressable Panel
If access 2 or 3 is active and the installer do not perform action for 30 seconds, the
panel automatically returns in access level 1.
2.1.2) LED indication Description
LED Name
Activation
Action
Buzzer Action
Colour
General Fire
In case of fire alarm
event from automatic
detector, call point,
evacuation or external
device connected to
panel input.
Constantly ON
Constantly ON
Red
General Fault
In case of any fault in
the system.
Constantly ON
Pulse Sound
Yellow
System Fault
In case of CPU crash.
Constantly ON
Pulse Sound
Yellow
Delay
In case of active delay in
the system.
Constantly ON
One Pulse
Sound
Yellow
Disable
If there is active delay in
the system.
Constantly ON
One Pulse
Sound
Yellow
Test
If there is active test
procedure in the system.
Constantly ON
One Pulse
Sound
Yellow
Sounder
Fault/Disable
If there is a fault in the
sounder output circuit or
the output is disabled.
Blinking/
Constantly ON
Pulse Sound
Yellow
Fire Confirmed
If Input 1 is activated.
See page 3
Constantly ON
One Pulse
Sound
Yellow