SIMPO Addressable Fire Alarm Panel Maintenance Menus
10
3. MAINTENANCE MENUS
The Maintenance Menus are accessible after entering a Maintenance access code (default 2222).
Maintenance Menus Description
Silence buzzer
Deactivating Internal Buzzer.
Silence Sounders
Deactivating the Sounders.
During active fire alarms and deactivated/ silenced sounders the LED next the button is
lighting up.
Reset
Resetting the panel without switching off the main and backup power supplies.
Evacuation
Activating Evacuation alarm signal; the sounders will activate immediately overriding all
introduced delays.
Test
General test for operability of all LEDs and internal buzzer.
View history LOG
Viewing the LOG file for all events; printing of all or separate events.
Zones
Reviewing the Zone status; zone test for operability, disablement.
Devices Setup
Reviewing the Device status; disablement.
Panel outputs
Disablement of built-in panel outputs: SOUNDERS, EXITING, FIRE, FAULT, RELAY
OUTPUTS.
General Settings:
General settings common for the panel.
Time/ Day
Setting the current time and date.
Day/ Night alarm mode
Reviewing of the set Day/ Night alarm mode.
Panel settings
Changing the menu language, setting the backlight brightness; entering disablements.
Delay Т1
Setting the Delay Т1.
Sounders mode
Reviewing of the set operation of SOUNDER outputs.
Company logo
Enter company information for the main screen
Save configuration
Saving the set system configuration.
Software revision
Reviewing the current software revision.
Active isolators
Reviewing the activated isolators in the system.
Access level 1
Return to Access Level 1.
3.1. View History Log Menu
This menu allows the technician to review and print the system events recorded in the panel memory log file. The
capacity of the panel memory log file is 10000 events.
After entering the menu, the screen displays:
The following general information is displayed in the main screen of
VIEW LOG menu:
Total Entries - Shows the total number of the recorded events in the
memory log file.
Total Alarms Count - Shows the total number of the registered alarm
events.
Use the functional digit buttons to enter the respective submenu.