GENERAL INSTALLATION
OPA 465960 RKTG-P (ECO)
Air Cooled Packaged Units - Reverse Cycle - R410A
Installation & Maintenance
1. GENERAL
Temperzone OPA Outdoor Air Cooled Packaged units.
Follow these instructions to ensure the optimum
performance, reliability and durability.
Units must be installed in accordance with all national and
regional regulations and bylaws. National Health and Safety
regulations must be followed to avoid personal injuries.
The appropriate local permits must be acquired and
adhered to.
Local regulations on maximum boundary noise need to
be considered when positioning the unit.
2. INSTALLATION
Refer to dimension diagrams below for minimum clearances.
If multiple units are to be placed side-by-side then allow at
least 2m between coil faces. (refer g. 1)
2.1 Mounting
The unit should be fastened to a rm at horizontal
base using the holes supplied in the mounting
channels. When the unit is being installed on a roof it is
recommended that the unit is installed on a substantial
structure with vibration isolating springs beneath the
unit. These springs are not supplied with the unit.
Flexible duct connections are recommended between
the supply and return ducts and the unit.
Unit is shipped with wooden blocks installed under the
compressors. Ensure these blocks are removed from
the compressor feet prior to starting the unit
(not required for operation).
Factory lter slides are tted, access to the lter access
door should be considered when designing return
and supply air ductwork. Access to the lters can still
be achieved by removing the return air access door,
however it is imperative that the rubber insulating
washers be retted to the screws prior to replacing
the panel.
2.2 Condensate Drain
The condensate drain should be ‘U’ trapped outside the
unit. The trap should have a vertical height of at least
100 mm. The drain should have a slope of at least 1 in
50 and must not be piped to a level above the unit drain
pipe. (refer g. 2)
Figure 1.
OPEN
DRAIN
MINIMUM
SLOPE
20 mm PER m
(1 IN 50)
100 mm
MINIMUM
200 mm
APPROX.
'U' TRAP
100 mm
APPROX.
VENT PIPE
FOR LONG
CONDENSATE
DRAIN RUNS
Figure 2.
SUPPLY
AIR
RETURN
AIR
OUTDOOR
AIR FLOW
OUTDOOR
AIR FLOW
OPTIONAL
WEATHER
HOOD
1000 MIN. CLEARANCE
500 MIN. CLEARANCE
ELECTRICAL
ACCESS
PANEL
1000 MIN.
CLEARANCE
FOR FILTER
ACCESS
500 MIN. CLEARANCE
2000 MIN. CLEARANCE
1000 MIN. CLEARANCE
FAN
ACCESS
PANEL

Questions and Answers

Summary

General Information

Unit Installation Compliance

Units must be installed in accordance with national/regional regulations and bylaws.

Installation Guidelines

Electrical Wiring and Controls

Electrical Work Safety

Electrical work must be done by a qualified electrician; danger of live electrical connections.

Unit Controller (UC6) Functions

UC6 controller provides system protection, capacity control, superheat regulation, and serial communications.

Startup Procedure Guide

Pre-Start-Up Checks

Perform checks like mains isolation, crankcase heater delay, compressor security, fan motor, wiring, and filters.

Commissioning Process

Includes checking supply voltage, compressor rotation, current draw, and refrigerant pressures.

Unit Operation and Protections

Operational Features and Protections

Covers remote on/off, variable duty control, and various protection mechanisms like HP, LOR, FROST, HDT.

Operation Faults and Modes

Lock-out Reset Procedure

Lock-out conditions can be reset by removing mains power or using a UC6 service tool.

Maintenance Schedule and Tasks

Routine Maintenance Checks (Monthly to Yearly)

Covers monthly, three-monthly, six-monthly, and yearly checks for filters, drains, oil, pressures, and cleaning.

Troubleshooting Common Issues

OPA 465 RKTG-P Wiring Schematic

OPA 550 RKTG-P Wiring Schematic

OPA 705 RKTG-P Wiring Schematic

OPA 800 RKTG-P Wiring Schematic

OPA 855 RKTG-P Wiring Schematic

OPA 960 RKTG-P Wiring Schematic

TemperZone OPA RKTG-P Series Specifications

General IconGeneral
TypePackaged Air Conditioner
RefrigerantR410A
Noise Level (Indoor Unit)Not applicable
Net Weight (Indoor Unit)Not applicable
Dimensions (Indoor Unit)Not applicable