Chapter 3 Communications
TestEquity F4T Controller Page 19
SCPI commands (continued)
Description
SCPI Command
SCPI Values
R/W
Commands to Support Profiles
Select a profile
:PROGram:SELected:NUMBer <value>
1-40
W
Query the current profile name
:PROGram:SELected:NAME?
<string value>
R
Set the current profile step
:PROGram:SELected:STEP <value>
1-50
W
Start the current profile
:PROGram:SELected:STATe STArt
W
Terminate the current profile
:PROGram:SELected:STATe STOP
W
Pause the current profile
:PROGram:SELected:STATe PAUSe
W
Resume the current profile
:PROGram:SELected:STATe RESume
W
Query active profile number
:PROGram[:SELected]:NUMBer?
R
Query profile state
:PROGram[:SELected]:STATe?
R
Query current profile set point
:PROGram[:SELected]:SPOint#?
R
Query current profile step number
:PROGram[:SELected]:STEP?
R
Query current profile step type
:PROGram[:SELected]:STEP:TYPE?
R
Query current profile step time elapsed
:PROGram[:SELected]:STEP:TIME:ELApsed?
R
Query current profile step time remain
:PROGram[:SELected]:STEP:TIME:REMain?
R
Identification
*IDN?
"Watlow Electric",<string value>,<integer value>,<string value>
(manufacturer)
R
(model number)
(serial number)
(firmware level)