Section 3 - Software Description
(10/08) 3 - 13
Accessing Additional Main Menu Screens
1. After all (if any) alarms are viewed, press the
Select key, until a flashing [dEF] is viewed.
This indicates the Manual Defrost function. To
change the [deF] setting, press the Enter key,
then use the Up Arrow or Down Arrow keys to
change the defrost setting to ON or OFF.
2. Press the Select key. An [SP] appears, to
indicate the setpoint temperature for the
return air temperature in the single or
primary load compartment of the vehicle.
To change the [SP] setting, do the following:
Press the Up Arrow key to increase the
return air temperature by 1-degree
increments.
Press the Down Arrow key to decrease the
return air temperature by 1-degree
increments.
Press and release the SELECT key to return
to the Standard Display.
NOTE: If the Select key is not pressed within
20 seconds to select a new setpoint
temperature, the unit continues to operate at
the original setpoint temperature.
3. For vehicles with two compartments and
bi-temperature functions, the screen displays
[SP2]. This indicates the setpoint for the
return air temperature in the second (remote)
compartment.
To change the [SP2] setting, do the
following:
Press the Up Arrow key to increase the
return air temperature by 1-degree
increments.
Press the Down Arrow key to decrease the
return air temperature by 1-degree
increments.
4. Press and release the Select key to return to
the Standard Display.
NOTE: If the Select key is not pressed within
20 seconds to select a new setpoint
temperature, the unit continues to operate at
the original setpoint temperature.
Leaving the Main Menu
Leaving the Main Menu can be accomplished in
several ways.
Press the Select key until you have toggled
through all of the Main Menu screens.
Turn the unit off and back on. The In-cab
Control Box exits the Main Menu, at any
point in the scrolling sequence, and returns
to the Standard Display.
Allow the display to time out. The In-cab
Control Box automatically exits the Main
Menu and return to the Standard Display, if
no key is pressed for 20 seconds.
- C - Total communications failure between the
microprocessor in the In-cab Control Box
and the microprocessor(s) in the ECM.
Unit is not able to turn on and operate.
The [- C -] alarm code is not part of the
Main Menu alarms. When a Main Menu
alarm occurs, the In-cab Control Box can
communicate with the ECM, and I/O and
parameter statuses can be checked.
When the [- C -] alarm code occurs, there
are no communications between the
In-cab Control Box and the ECM, and I/O
and parameter statuses cannot be
checked at the In-cab Control Box.
Alarm
Code
Alarm
Description

Table of Contents

Other manuals for Thermo King B Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Thermo King B Series and is the answer not in the manual?

Thermo King B Series Specifications

General IconGeneral
RefrigerantR-404A
ApplicationTruck
Voltage12V or 24V DC
Heating CapacityVaries by model
DimensionsVaries by model
Noise LevelVaries by model

Related product manuals