49
HEATING CIRCUIT
Select HEATING CIRCUIT on
the user menu and press the
SET button
HEATING CIRCUIT
- HEATING CIRCUIT 1
- HEATING CIRCUIT 2
- HEATING CIRCUIT 3
Chose HEATING CIRCUIT1
HEATING CIRCUIT1
NOT AVALIABLE
PUMP
PUMP+MIXER
Chose PUMP
HEATING CIRCUIT 1
HC. FLOW SET TEMP.
70
WORK : 77
Set the default temperature in
the heating circuit.
Note, the temperature is the
same for all heating circuits,
EXCEPT circuit with mixing valve
HEATING CIRCUIT
HEAT CIRC. RES.HEAT USE TO
5
*C
WORK: 5 *C
Turn-OFF temperature
(STOP) of the circulation
pump in the heating circuit.
HEATING CIRCUIT
HEAT CIRC. PUMP ON AT
55
*C
WORK: 55 *C
Turn-on temperature
(START) of the circulation
pump in the heating circuit.
HEAT CIRCUIT
Heat Circ.Hyst
2 *C
WORK: 4 *C
Adjust the heating circuit
hysteresis