Thytronic NV10B - Primary Voltage Setting Adjustments

Thytronic NV10B
118 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CHARACTERISTICS
41
NV10B - Manual - 04 - 2022
Example 1
The U
np
setting must be adjusted to: U
np
= U
ng
= 6.0 kV
Example 2
The U
np
setting must be adjusted to: U
np
= U
ng
= 6 kV
Example 3
The U
np
setting must be adjusted to: U
np
= U
ng
= 400 V
Residual primary voltage U
Enp
This parameter affects the measure of the direct residual voltage when the primary measurement
reading mode is selected.
If the formerly indications concerning the relay nominal residual voltage U
En
are complied, then the
U
Enp
setting must be adjusted to (effective for insulated neutral or impedance-ground connected
grids):
U
Enp
= √3 ∙ grid nominal voltage [V].
Example 1
Es1-Ung.ai
K
TV
=
/
/
V
V
6000
3
100 3
= 60
/
/
V
V
6000
3
100 3
= 60
Grid nominal voltage U
ng
= 6.0 kV
VTs ratio: K
TV
=
Relay nominal voltage U
n
= 58 V
U
n
= 58 V
U
ng
= 6.0 kV
52
NV10B
Es2-Ung.ai
K
VT
=
/
/
V
V
6000
3
100 3
= 60
/
/
V
V
6000
3
100 3
= 60
Grid nominal voltage U
ng
= 6 kV
VTs ratio: K
TV
=
Relay nominal voltage U
n
= 100 V
U
n
= 100 V
U
ng
= 6 kV
52
NV10B
Es3a-Un.ai
U
ng
= 400 V
U
n
= 400 V
52
NV10B
Es-UEnp.ai
K
VT
=
/
/
V
V
10000
3
3
100 3
= 100 ·
/
/
V
V
10000
3
3
100 3
= 100 ·
Grid nominal voltage U
ng
= 6.9 kV
VT ratio: K
VT
=
Relay residual nominal voltage U
En
= 69 V
U
En
= 69 V
/
U
ng
= 6.9 kV
52
NV10B
Insulated or impedance-ground neutral