CHARACTERISTICS
42
NV10B - Manual - 04 - 2022
The U
Enp
setting must be adjusted to: U
Enp
= √3 · U
ng
= √3 · 6900 V = 11900 V
Example 2
The U
Enp
setting must be adjusted to: U
Enp
= √3 · U
ng
= √3 · 10000 V = 17300 V
• Measurement reading mode
Measures may be displayed according the following operating modes:
- With RELATIVE setting all measures are related to the nominal value,
- With PRIMARY setting all measures are related to the primary value.
Es3-UEn.ai
K
VT
=
/ V
V
11000
3
3
100
= 110 /
K
VT
=
/ V
V
11000
3
3
100
= 110 /
Grid nominal voltage U
ng
= 10 kV
Ratio of voltage transformer connected from star neutral to ground:
NV10B
U
ng
= 10 kV
U
En
= 91 V