Piping size and Y-joint
Maximum real piping length between valve kit and Dx coil is up to 16'5" (5 m)
4-3. Piping size and Y-joint
(Unit: in (mm))
DX-COIL type Normol
Ton Y-joint (A, B)
20 RBM-BY205E
22 ~ 50 RBM-BY305E
DX COIL
type
Pipe diameter
(1) Gas pipe (2) Liquid pipe (3) Liquid pipe
Ton Outer diameter
0.6 ~ 5
5/8" (15.9) 3/8" (9.5)
6 3/4" (19.1)
1/2" (12.7)
8 7/8" (22.2)
10
1.1/8" (28.6)
12 ~ 14
5/8" (15.9)
16
18
3/4" (19.1)
20 ~ 22
1.3/8" (34.9)
24 ~ 27
28 ~ 36
1.1/2" (38.1)
38 ~ 40
7/8" (22.2)
- 20 -