27
Advanced setup
For the brave!
Setup reset
For setup reset send the SMS “90” to the controller. Combi Control
responds with SETUP report:
“Owner: All; Users: All; Pump: All; Ring 2,2,2; Param: 5, 24, 180”.
This means Owner is not specified; all users can send commands;
the pump model is not specified, call commands are set to default;
“LOW TEMPERATURE” message will be sent when room temperature
drops below 5 °C , “NO POWER” message blackout is in 24 hours and the
“SERVICE” alarm message interval is 180 days.
Setup SMS command
you send
Response
SMS
Controller function you activate
90 SETUP
Setup reset (Owner deleted)
and controller restart
93 VERSION First time Owner number entry