Electronic Operator Interface (EOI)
Rotary 
Encoder
LCD  Screen
Wizard: RunWizard: Run
Run nowRun now
Run next timeRun next time
Manually configure (Finish)Manually configure (Finish)
Startup Wizard Screen
4. Programming
The operating parameters displayed on the LCD 
screen may be selected, viewed , or change d 
using the 
Electronic Operator Interface
 
(EO I). To 
change a setting turn the 
Rotary  Enco der
 
to 
highlight the desired 
Pr imar y Menu  
item
 
(repeat 
for 
Sub Me nu 
 items as required). Select the item 
to be changed  and press the 
Rotary Encoder
 to 
enter the 
Edit
 mode — the encoder acts as the 
enter key.
 
Set the paramet er to the new  value. To 
exit the setting without saving a change press 
the 
ESC
 key while the param eter is in the reverse video mod e (dark bac kgroun d/ light text).
 
Press the 
Rotary Encoder
 to accept the  change.
 
Startup Wizard
Upon initial power up or factory reset the 
Startup Wizard
 will start automatically.
The 
Star tu p Wiz ar d
 will query the user to select 
one of the following items: 
Run No w
,
 Run Next  
Time
, or 
Manu a lly Co nf igur e
.
Click 
Run Ne xt Tim e
 or 
M anua lly Co nf igur e
 
to 
skip setup. The ASD may be setup at a later 
time by directly accessing each of the startup parameters via the
 Program Menu
, the 
associated 
Direct Access Number
, or by running the 
Star tu p  Wiz ar d
 from the programming 
menu.
Click
 Ru n No w
 to setu p th e ASD n o w. The 
Startup Wizard
 will take the user through the 
parameters listed below.
At any point, the user may click 
Next
 to skip a param eter or click 
Finish
 to close the 
Startup 
Wizard
. 
Click
 
Finish
 
when  complete.
Startup Wizard Parameters
Direct 
Acce ss 
Number
Star tu p  Wiz ar d 
Parameter
Description
F405
Voltage/Frequency  
Rating of Motor
Used to input the nameplated voltage and frequency 
of the motor being used. 
F012 Upper Limit Frequency
Sets the highest freque ncy that the ASD will  accept as 
a frequency command or frequency setpoint. 
F013 Lower  Limit Frequency
Sets the low est frequ ency t hat the  ASD will accept as 
a frequency command or frequency setpoint. 
F000
Automatic Acceleration/
Decelera tion Setting
Adjusts the acceleration and deceleration rates 
according to the applied load. 
F009 Acceleration Time
Specifies the time in seconds for the output of the 
ASD to go  from  0.0 Hz to the Ma x imum  Freq uency.
F010 Deceleration Time
Specifies the time in seconds for the output of the 
ASD to go from the Maximum Frequency to 0.0 Hz.
F015 Volts Per Hert z Setting
Establishes the relationship between the output 
frequency and the output voltage of the ASD. 
F406 Motor Current Rating
Allows the user to input the Full-Load Amperage 
(FLA) of the motor. 
F407 Motor RPM
Used to input the nameplated rated speed (RPM) of 
the motor being used.
F003 Command Source
Establishes  the source of input commands (i.e., Run, 
Stop, Jog, etc.).
F004 Frequency Source
Establishes the source of the primary frequency 
reference.
F701 Display Unit
Sets the unit of me asure for current  and  voltage 
value s displayed on the EOI.
 
Note
:
 
Use the
 
Motor Information 
outline provided in this guide to record and retain 
information about the motor for future use.
Programming Options:
Direct Access to P arameters
Each parameter may be viewed or changed by  entering the parameter number of the setting 
at the 
Direct Acc ess
 
Menu
 
via Program 
 D irect Access 
 
Applicable Parameter Number
.
Changed From Default
A listing of all the
 
parameters that 
have been changed from the default 
setting may be viewed sequ entially 
by accessing the 
Changed From 
Default
 screen
 
via
 
Program
  
Utilities
  
Changed From Default.
Press the 
Rotary Encoder
 w hile 
stopped at a changed parameter to 
display the settings of the changed 
parameter. Press the 
Rotary Encoder
 
to enter the 
Edit
 mode. Turn the 
Rotar y Enco der
 to change the 
parameter setting.
Press the 
ESC
 key w hile  the s ystem is 
performing a 
Changed  From  De fa u lt 
search to terminate the search.
W hen finished searching, press the 
ESC
 key to take the menu back one 
level.
RR Analog Input
Frequ e ncy Mo de 1
 
(
F004
)
 
esta blishe s 
the user-selected so urce of the 
frequency-control input for the ASD. By default it is set to the RR terminal. 
This input terminal may be programmed to control the speed or torque of the motor
.
The 
Scaling
, 
Gain
, and 
Bias
 of this terminal may be adjusted for application-specific suitability 
(see 
F210
 – 
F215
).
V/I Analog Input
Frequ e ncy  M o de 1
 
(
F004
)
 
establishes th e user-selected source of the frequency-control input 
for the ASD.
Th is is an isolated input terminal. This termin al ma y be program med  to contro l the speed or 
tor q u e of the mot o r an d  m us t  b e set to  r ecei ve  e it he r curr en t  (
SW301
 set to
 I
)  or voltage 
(
SW 301
 set to 
V
).
The
 
Scaling
, 
Gain
, and 
Bias
 of this terminal may be adjusted for application-specific suitability 
(see 
F201
 – 
F206
).
FM Analog Output
By defaul t, the 
FM
 
analog
 
output terminal produces an output current or voltage that is 
proportional to the output frequency of the ASD or of the magnitude of the function  assigned 
to th is term ina l (select curren t or  voltage a t 
F681
). The prog rammable  functions for this 
ou tpu t terminal ar e listed  in t he 
G9 ASD Installation and Operation Manual
. 
FM 
Term inal Setup Paramete
rs:
F005
 
—  Set Funct ion
F006
 
—  Calibra t e Te rm in a l S el ecti on
F681
 
—  Voltage /Cur ren t Switching  Selection
F682
 
—  Respo nse Po larity Selection
F683
 —  Bias Ad justmen t
AM Analog Output
By defaul t, the 
AM
 
analog
 
output terminal produces an 0-20
 
mA current that is proportional 
to the output current of the ASD or of the magnitude of the function assigned to the terminal. 
The programmable functions for this output terminal are listed in the 
G9 ASD  Installation and 
Operation Manual
. 
AM  Terminal Setup Paramete
rs:
F670
 
—  Set Funct ion
F671
 
—  Calibra t e Te rm in a l S el ecti on
F685
 
—  Respo nse Po larity Selection
F686
 
— Bias Adjustment
For a  complet e listing of discrete and analog inputs/outputs see the 
G9 ASD Quick Start Guide. 
Discrete
 
Terminal Na mes
Direct 
Access 
Number
Termina l
Default 
(Where 
Programmable)
F114 RES Reset
F111 F Forward Run
F112 R Reverse Run
F115 S1 Preset Speed 1
F116 S2 Preset Speed 2
F117 S3 Preset Speed 3
F118 S4 Preset Speed 4
F113 ST Sta nd b y
F676 FP Frequency Pulse
— +SU Refe ren ces CC
— CC Control Common