Electronic Operator Interface (EOI)
Rotary
Encoder
LCD Screen
Wizard: RunWizard: Run
Run nowRun now
Run next timeRun next time
Manually configure (Finish)Manually configure (Finish)
Startup Wizard Screen
4. Programming
The operating parameters displayed on the LCD
screen may be selected, viewed , or change d
using the
Electronic Operator Interface
(EO I). To
change a setting turn the
Rotary Enco der
to
highlight the desired
Pr imar y Menu
item
(repeat
for
Sub Me nu
items as required). Select the item
to be changed and press the
Rotary Encoder
to
enter the
Edit
mode the encoder acts as the
enter key.
Set the paramet er to the new value. To
exit the setting without saving a change press
the
ESC
key while the param eter is in the reverse video mod e (dark bac kgroun d/ light text).
Press the
Rotary Encoder
to accept the change.
Startup Wizard
Upon initial power up or factory reset the
Startup Wizard
will start automatically.
The
Star tu p Wiz ar d
will query the user to select
one of the following items:
Run No w
,
Run Next
Time
, or
Manu a lly Co nf igur e
.
Click
Run Ne xt Tim e
or
M anua lly Co nf igur e
to
skip setup. The ASD may be setup at a later
time by directly accessing each of the startup parameters via the
Program Menu
, the
associated
Direct Access Number
, or by running the
Star tu p Wiz ar d
from the programming
menu.
Click
Ru n No w
to setu p th e ASD n o w. The
Startup Wizard
will take the user through the
parameters listed below.
At any point, the user may click
Next
to skip a param eter or click
Finish
to close the
Startup
Wizard
.
Click
Finish
when complete.
Startup Wizard Parameters
Direct
Acce ss
Number
Star tu p Wiz ar d
Parameter
Description
F405
Voltage/Frequency
Rating of Motor
Used to input the nameplated voltage and frequency
of the motor being used.
F012 Upper Limit Frequency
Sets the highest freque ncy that the ASD will accept as
a frequency command or frequency setpoint.
F013 Lower Limit Frequency
Sets the low est frequ ency t hat the ASD will accept as
a frequency command or frequency setpoint.
F000
Automatic Acceleration/
Decelera tion Setting
Adjusts the acceleration and deceleration rates
according to the applied load.
F009 Acceleration Time
Specifies the time in seconds for the output of the
ASD to go from 0.0 Hz to the Ma x imum Freq uency.
F010 Deceleration Time
Specifies the time in seconds for the output of the
ASD to go from the Maximum Frequency to 0.0 Hz.
F015 Volts Per Hert z Setting
Establishes the relationship between the output
frequency and the output voltage of the ASD.
F406 Motor Current Rating
Allows the user to input the Full-Load Amperage
(FLA) of the motor.
F407 Motor RPM
Used to input the nameplated rated speed (RPM) of
the motor being used.
F003 Command Source
Establishes the source of input commands (i.e., Run,
Stop, Jog, etc.).
F004 Frequency Source
Establishes the source of the primary frequency
reference.
F701 Display Unit
Sets the unit of me asure for current and voltage
value s displayed on the EOI.
Note
:
Use the
Motor Information
outline provided in this guide to record and retain
information about the motor for future use.
Programming Options:
Direct Access to P arameters
Each parameter may be viewed or changed by entering the parameter number of the setting
at the
Direct Acc ess
Menu
via Program
D irect Access
Applicable Parameter Number
.
Changed From Default
A listing of all the
parameters that
have been changed from the default
setting may be viewed sequ entially
by accessing the
Changed From
Default
screen
via
Program
Utilities
Changed From Default.
Press the
Rotary Encoder
w hile
stopped at a changed parameter to
display the settings of the changed
parameter. Press the
Rotary Encoder
to enter the
Edit
mode. Turn the
Rotar y Enco der
to change the
parameter setting.
Press the
ESC
key w hile the s ystem is
performing a
Changed From De fa u lt
search to terminate the search.
W hen finished searching, press the
ESC
key to take the menu back one
level.
RR Analog Input
Frequ e ncy Mo de 1
(
F004
)
esta blishe s
the user-selected so urce of the
frequency-control input for the ASD. By default it is set to the RR terminal.
This input terminal may be programmed to control the speed or torque of the motor
.
The
Scaling
,
Gain
, and
Bias
of this terminal may be adjusted for application-specific suitability
(see
F210
F215
).
V/I Analog Input
Frequ e ncy M o de 1
(
F004
)
establishes th e user-selected source of the frequency-control input
for the ASD.
Th is is an isolated input terminal. This termin al ma y be program med to contro l the speed or
tor q u e of the mot o r an d m us t b e set to r ecei ve e it he r curr en t (
SW301
set to
I
) or voltage
(
SW 301
set to
V
).
The
Scaling
,
Gain
, and
Bias
of this terminal may be adjusted for application-specific suitability
(see
F201
F206
).
FM Analog Output
By defaul t, the
FM
analog
output terminal produces an output current or voltage that is
proportional to the output frequency of the ASD or of the magnitude of the function assigned
to th is term ina l (select curren t or voltage a t
F681
). The prog rammable functions for this
ou tpu t terminal ar e listed in t he
G9 ASD Installation and Operation Manual
.
FM
Term inal Setup Paramete
rs:
F005
Set Funct ion
F006
Calibra t e Te rm in a l S el ecti on
F681
Voltage /Cur ren t Switching Selection
F682
Respo nse Po larity Selection
F683
Bias Ad justmen t
AM Analog Output
By defaul t, the
AM
analog
output terminal produces an 0-20
mA current that is proportional
to the output current of the ASD or of the magnitude of the function assigned to the terminal.
The programmable functions for this output terminal are listed in the
G9 ASD Installation and
Operation Manual
.
AM Terminal Setup Paramete
rs:
F670
Set Funct ion
F671
Calibra t e Te rm in a l S el ecti on
F685
Respo nse Po larity Selection
F686
Bias Adjustment
For a complet e listing of discrete and analog inputs/outputs see the
G9 ASD Quick Start Guide.
Discrete
Terminal Na mes
Direct
Access
Number
Termina l
Default
(Where
Programmable)
F114 RES Reset
F111 F Forward Run
F112 R Reverse Run
F115 S1 Preset Speed 1
F116 S2 Preset Speed 2
F117 S3 Preset Speed 3
F118 S4 Preset Speed 4
F113 ST Sta nd b y
F676 FP Frequency Pulse
+SU Refe ren ces CC
CC Control Common
T he Customer Support Center is open from 8 a.m. 5 p.m. (CST), Monday Friday. The Center’s toll free number is
(800) 231-1412. For after-hours support follow the directions in the outgoing message when calling.