– 19 –
7. COMMUNICATION TYPE, MODEL NAMES AND THE
MAXIMUM NUMBER OF CONNECTABLE UNITS
7-1. This air conditioning (U series) has new communication specifications, and TU2C-
Link (U series) and TCC-Link (other than U series) differ in a communication type.
For the communication type and the model names such as each unit or remote
controllers, refer to the following table.
7-2. If TU2C-Link (U series) is combined with TCC-Link (other than U series), the wiring
specifications and the maximum number of connectable indoor units during group
control operation will be changed.
(1) For wiring specifications, carry out the installation, maintenance, or repair according to the attached
Installation Manual.
(2) For a communication type combination and the max. number of connectable Hot Water Module, refer
to the following table.
• Only when all outdoor unit, indoor unit and remote control are a U series, communication method is
TU2C-LINK, and the maximum number of connectable units will be 16.
Communication type
TU2C-Link
(U series and future models)
TCC-Link
(Other than U series)
Outdoor unit
MMY-MUP***
↑
This letter indicates U series model.
Other than U series
MMY-MHP*** , MMY-MAP***
MCY-MHP***
Indoor unit
(Hot Water Module)
MM* -UP***
↑
This letter indicates U series model.
Other than U series
MM* -AP***
Wired remote controller
RBC-A**U***
↑
This letter indicates U series model.
Other than U series
U series outdoor unit : SMMS-u (MMY-MUP*** )
Other than U series outdoor unit : SMMS-i, SMMS-e etc. (MMY-MAP*** )
Remote
controller
wiring
L
L1
HWM
HWM
Remote
controller
L2
HWM
For the maximum number
of connectable units, refer
to the following table.
Remote controller
inter-unit wiring
Ln
HWM
The combination of unit type and the number of the maximum connection of a communication method
Unit type
Outdoor unit U series U series U series U series * * * *
Indoor unit (HWM) U series U series * * U series U series * *
Remote controller U series * U series * U series * U series *
Communication type TU2C-Link TCC-Link
Maximum number
of connectable units
16 8
* Other than U series