3
1. DIFFERENT POINTS OF THE MAIN PARTS
This model is added with the passive filter to the fan driving circuit of the existing model and then Type name is
changed. (“-E” is added to the end of the Type name.)
1. Newly changed contents
Addition of passive filter against the harmonic
2. Contents change of running
1) Reduction in refrigerant amount
Applied models: MMY-MAP0801HT8 (-E), MAP1001HT8 (-E), MAP1201HT8 (-E)
(Only for SMMS heat pump models) Unit: kg
2) Change of oil tank appearance
Applied models: SMMS series, SHRM series
<Reference: Product Bulletin No.2007-13>
1
2
Item
Power supply P.C.
board for fan IPDU
Passive filter
Existing model
SMMS SHRM
MCC-1439-05
None
Model in this time
SMMS SHRM
MCC-1439-06
Addition of connector
to connect the passive filter
Electrolytic capacitor (MCC-1580),
Resistance, Diode, Reactor (CH-68)
System HP
5
6
8
10
12
Existing model
SMMS
—
—
12.5
12.5
12.5
Model in tis time
SMMS
—
—
12.0
12.0
12.0
Tank type of Oil tank (past)
(Appearance)
Tube type of Oil tank (current)
(Appearance)
(Layout)
– Rear view —
(Layout)
– Rear view —