EasyManua.ls Logo

Toshiba MMY-MAP0802FT8-E - Key Differences in Main Parts; Newly Changed Contents: Passive Filter Addition; Changes in Refrigerant Amount; Oil Tank Appearance Change

Toshiba MMY-MAP0802FT8-E
45 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3
1. DIFFERENT POINTS OF THE MAIN PARTS
This model is added with the passive filter to the fan driving circuit of the existing model and then Type name is
changed. (“-E” is added to the end of the Type name.)
1. Newly changed contents
Addition of passive filter against the harmonic
2. Contents change of running
1) Reduction in refrigerant amount
Applied models: MMY-MAP0801HT8 (-E), MAP1001HT8 (-E), MAP1201HT8 (-E)
(Only for SMMS heat pump models) Unit: kg
2) Change of oil tank appearance
Applied models: SMMS series, SHRM series
<Reference: Product Bulletin No.2007-13>
1
2
Item
Power supply P.C.
board for fan IPDU
Passive filter
Existing model
SMMS SHRM
MCC-1439-05
None
Model in this time
SMMS SHRM
MCC-1439-06
Addition of connector
to connect the passive filter
Electrolytic capacitor (MCC-1580),
Resistance, Diode, Reactor (CH-68)
System HP
5
6
8
10
12
Existing model
SMMS
12.5
12.5
12.5
Model in tis time
SMMS
12.0
12.0
12.0
Tank type of Oil tank (past)
(Appearance)
Tube type of Oil tank (current)
(Appearance)
(Layout)
– Rear view —
(Layout)
– Rear view —

Related product manuals