165
*1 Only a part of indoor unit types is installed with the discharge temperature sensor. This temperature is not displayed for other types.
*2 When the units are connected to a group, data of the header indoor unit only can be displayed.
*3 The first digit of an CODE No. indicates the outdoor unit number.
*4 The upper digit of an CODE No. -4 indicates the outdoor unit number.
1 , 5 ... U1 outdoor unit (Header unit)
2 , 6 ... U2 outdoor unit (Follower unit 1)
3 , 7 ... U3 outdoor unit (Follower unit 2)
4 , 8 ... U4 outdoor unit (Follower unit 3)
*5 Only the CODE No. 5* of U1 outdoor unit (Header unit) is displayed.
CODE No. Data name Display format Unit Remote controller display example
Indoor unit data *
2
00 Room temperature (During control) ×1 °C
[0024]=24°C
01 Room temperature (Remote controller) ×1 °C
02 Indoor suction temperature (TA) ×1 °C
03 Indoor coil temperature (TCJ) ×1 °C
04 Indoor coil temperature (TC2) ×1 °C
05 Indoor coil temperature (TC1) ×1 °C
06 Indoor discharge temperature (TF)
*
1
×1 °C
08 Indoor PMV opening ×1/10 pls [0150]=1500pls
System data
0A No. of connected indoor units ×1 unit [0048]=48 units
0B Total horsepower of connected indoor units ×10 HP [0415]=41.5HP
0C No. of connected outdoor units ×1 unit [0004]=4 units
0D Total horsepower of outdoor units ×10 HP [0420]=42HP
CODE No.
Data name Display format Unit Remote controller display example
U1 U2 U3 U4
Outdoor unit individual data 1 *
3
10 20 30 40 High-pressure sensor detention pressure (Pd) ×100 MPa
[0123]=1.23MPa
11 21 31 41 Low-pressure sensor detention pressure (Ps) ×100 MPa
12 22 32 42 Compressor 1 discharge temperature (Td1) ×1 °C
[0024]=24°C
13 23 33 43 Compressor 2 discharge temperature (Td2) ×1 °C
14 24 34 - Compressor 3 discharge temperature (Td3) ×1 °C
15 25 35 45 Suction temperature (TS) ×1 °C
16 26 36 46 Outdoor coil temperature 1 (TE1) ×1 °C
17 27 37 - Outdoor coil temperature 2 (TE2) ×1 °C
18 28 38 48 Temperature at liquid side (TL) ×1 °C
19 29 39 49 Outside ambient temperature (TO) ×1 °C
1A 2A 3A 4A PMV1 + 2 opening ×1 pls
[0500]=500pls
1B 2B 3B - PMV4 opening ×1 pls
1C 2C 3C 4C Compressor 1 current (I1) ×10 A
[0135]=13.5A
1D 2D 3D 4D Compressor 2 current (I2) ×10 A
1E 2E 3E - Compressor 3 current (I3) ×10 A
1F 2F 3F 4F Outdoor fan current (IFan) ×10 A
CODE No.
Data name Display format Unit Remote controller display example
U1 U2 U3 U4
Outdoor unit individual data 2 *
4
50 60 70 80 Compressor 1 revolutions ×10 rps
[0642]=64.2rps51 61 71 81 Compressor 2 revolutions ×10 rps
52 62 72 - Compressor 3 revolutions ×10 rps
53 63 73 83 Outdoor fan mode ×1 mode [0058]= 58 mode
54 64 74 84 Compressor IPDU 1 heat sink temperature ×1 °C
[0024]=24°C
55 65 75 85 Compressor IPDU 2 heat sink temperature ×1 °C
56 66 76 - Compressor IPDU 3 heat sink temperature ×1 °C
57 67 77 87 Outdoor fan IPDU heat sink temperature ×1 °C
58 - - - Heating/cooling recovery controlled
*
5
0: Normal
1: Recovery controlled
[0010]=Heating recovery controlled
[0001]=Cooling recovery controlled
59 - - - Pressure release
*
5
0: Normal
1: Release controlled
[0010]=Pressure release controlled
5A - - - Discharge temperature release
*
5
[0001]=Discharge temperature release controlled
5B - - -
Follower unit release
(U2/U2/U4 outdoor units)
*
5
[0100]=U2 outdoor unit release controlled
[0010]=U3 outdoor unit release controlled
[0001]=U4 outdoor unit release controlled
5F 6F 7F 8F Outdoor unit horsepower ×1 HP [0016]=16HP