Charging of refrigerant
• Keeping the valve of the outdoor unit closed, be sure to charge the liquid refrigerant into the service port at the
liquid side.
• If the specified amount of refrigerant cannot be charged, fully open the valves of the outdoor unit at liquid and
gas sides, operate the air conditioner in COOL mode, and then charge refrigerant into service port at the gas
side. In this time, choke the refrigerant slightly by operating the valve of the canister to charge liquid refrigerant.
• The liquid refrigerant may be charged suddenly, therefore be sure to charge refrigerant gradually.
Combined HP (HP) Combined outdoor units (HP)
C (Corrective amount
of refrigerant) (kg)
Standard type
8 8HP––– 1.5
10 10HP – – – 2.5
12 12HP – – – 3.5
14 14HP – – – 8.5
16 16HP – – – 10.5
18 10HP 8HP – – 0.0
20 10HP 10HP – – 3.0
22 12HP 10HP – – 5.0
24 12HP 12HP – – 7.5
26 16HP 10HP – – 8.5
28 16HP 12HP – – 9.5
30 16HP 14HP – – 11.5
32 16HP 16HP – – 12.5
34 12HP 12HP 10HP – 3.0
36 12HP 12HP 12HP – 4.0
38 16HP 12HP 10HP – 6.0
40 16HP 12HP 12HP – 7.0
42 16HP 14HP 12HP – 8.0
44 16HP 16HP 12HP – 10.0
46 16HP 16HP 14HP – 12.0
48 16HP 16HP 16HP – 14.0
High Efficiency type
16 8HP 8HP – – 0.0
24 8HP 8HP 8HP – -4.0
26 10HP 8HP 8HP – -4.0
28 10HP 10HP 8HP – -2.0
30 10HP 10HP 10HP – 0.0
32 8HP 8HP 8HP 8HP -6.0
34 10HP 8HP 8HP 8HP -6.0
36 10HP 10HP 8HP 8HP -6.0
38 10HP 10HP 10HP 8HP -6.0
40 10HP 10HP 10HP 10HP -5.0
42 12HP 10HP 10HP 10HP -4.0
44 12HP 12HP 10HP 10HP -2.0
46 12HP 12HP 12HP 10HP 0.0
48 12HP 12HP 12HP 12HP 2.0