– 284 –
(6) Set the dip switch (SW800) setting of the service board to match the switch setting from the original PCB.
- Set the dip switch (SW800) depending on the position of the IPDU within the electrical box, as shown in the
following diagram.
(7) Align the insulation sheet with the screw holes on the insulation sheet and the mounting holes on the PCB with
the PCB mounts. And fix the Compressor IPDU to the outdoor control unit by the spacers (
3).
(8) Screw the Compressor IPDU to the heat sink by the four
screws that were removed in step (3). If the screws are
loose, the effect component will generate heat, and cause it
to breakdown. Do not use an electric driver or an air driver.
As it can cause component damage. The torque of the
screws for DB01 is “0.55Nm” and it for Q201 is “1.2Nm”.
(9) Re-connect the connectors and fast-on terminals (
1). Be
sure that all the connectors and the fast-on terminals are
connected correctly and securely inserted.
(10)If the components on the PCB were bent during this
procedure, straighten them so they do not touch other
parts.
(11)Install the cover, then turn on the supply. Check the
operation.
ON
3421
ON
3421
ON
3421
ON OFF OFF OFF
ON
3421
OFF ON OFF OFF
ON
3421
ON ON OFF OFF
Dip Switch
(SW800)
Ex. MMY-MAP1004HT8P Ex. MMY-MAP1604HT8P
Compressor IPDU [Left Side]
For Compressor: 1
Dip switch (SW800) setting:
Compressor IPDU [Right Side]
For Compressor: 2
Dip switch (SW800) setting:
Compressor IPDU [Left Side]
For Compressor: 1
Dip switch (SW800) setting:
Compressor IPDU [Middle]
For Compressor: 2
Dip switch (SW800) setting:
Compressor IPDU [Right Side]
For Compressor: 3
Dip switch (SW800) setting:
FFOFFONOFFOFFOFFOFFONO
DB01
Q201