Chapter 5 Troubleshooting
6F8C1621
If the state display LED of the product displays anything different from the
normal display as described in "Table 1-1 Display details on the state display
LED and normal display" on page 5, or if any error is detected in the human
interface station, stop using it immediately and contact one of Toshiba's
service representatives.
To load the RAS data and system log, refer to engineering tool operation
manual.
Fault diagnosis method using the LEDs
Perform diagnosis by referring to the following table, LED and systemview,
systemlog, setting of station address swtich. Then operate remedy.
Table 5-1 Diagnosis using the LEDs
State Remedy
LINK-B
ACT -B
operation
setting error
Wrong setting of station address setting
switch
value any value other
than (00h) or FF(h).
Wrong setting of station address setting
switch
value unique in the
system.
parameter
mismatch
TC-net 100 parameters do not match
other node currently in transmission
with the engineering
tool.
overlap
-
-
Overlap of talker blocks is detected
registration of the
overlapping block.
Toshiba's service
representatives to
replace the module.
Loading the RAS data and system log
To load the RAS data and system log, refer to "Unified Controller nv series /
Integrated Controller V series nV-Tool (Basic) Operation Manual (6F8C1290)."
When an error occurs
Load the RAS data and system log before removing the module from the basic
unit.