106 Q9 ASD Installation and Operation Manual
Jump Frequency 1 Bandwidth
Program Special Controls
This parameter establishes a plus-or-minus value for Jump Frequency 1
(see F270 for more information on this parameter).
Direct Access Number — F271
Parameter Type — Numerical
Factory Default0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum30.00
Units — Hz
Jump Frequency 2
Program Special Controls
Same as Jump Frequency 1 (F270) and is used when multiple frequencies are to
be jumped (see the plus-or-minus value setting at F273). When multiple jump
frequencies overlap, the system will recognize the lowest and the highest
frequencies as one jump range.
Direct Access Number — F272
Parameter Type — Numerical
Factory Default0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
Jump Frequency 2 Bandwidth
Program Special Controls
This parameter establishes a plus-or-minus value for Jump Frequency 2 (F272).
Direct Access Number — F273
Parameter Type — Numerical
Factory Default0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 30.0
Units — Hz
Jump Frequency 3
Program Special Controls
Same as Jump Frequency 1 (F270) and is used when multiple frequencies are to
be jumped (see the plus-or-minus value setting at F275).
When multiple jump frequencies overlap, the system will recognize the lowest
and the highest frequencies as one jump range.
Direct Access Number — F274
Parameter Type — Numerical
Factory Default0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
Jump Frequency 3 Bandwidth
Program Special Controls
This parameter establishes a plus-or-minus value for Jump Frequency 3 (F274).
Direct Access Number — F275
Parameter Type — Numerical
Factory Default0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 30.0
Units — Hz
Preset Speed 8
Program Preset Speeds
This parameter assigns an output frequency to binary number 1000 and is
identified as Preset Speed 8. The binary number is applied to S1S4 of the
Terminal Board to output the Preset Speed (see F018 for more information on
this parameter).
Direct Access Number — F287
Parameter Type — Numerical
Factory Default0.00
Changeable During Run — Yes
Minimum — Lower-Limit (F013)
Maximum — Upper-Limit (F012)
Units — Hz
F271 F287