EasyManua.ls Logo

Toshiba Q9 - Page 117

Toshiba Q9
233 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Q9 ASD Installation and Operation Manual 107
Preset Speed 9
Program Preset Speeds
This parameter assigns an output frequency to binary number 1001 and is
identified as Preset Speed 9. The binary number is applied to S1S4 of the
Terminal Board to output the Preset Speed (see F018 for more information on
this parameter).
Direct Access Number — F288
Parameter Type — Numerical
Factory Default0.0
Changeable During Run — Yes
Minimum — Lower-Limit (F013)
Maximum — Upper-Limit (F012)
Units — Hz
Preset Speed 10
Program Preset Speeds
This parameter assigns an output frequency to binary number 1010 and is
identified as Preset Speed 10. The binary number is applied to S1S4 of the
Terminal Board to output the Preset Speed (see F018 for more information on
this parameter).
Direct Access Number — F289
Parameter Type — Numerical
Factory Default0.00
Changeable During Run — Yes
Minimum — Lower-Limit (F013)
Maximum — Upper-Limit (F012)
Units — Hz
Preset Speed 11
Program Preset Speeds
This parameter assigns an output frequency to binary number 1011 and is
identified as Preset Speed 11. The binary number is applied to S1S4 of the
Terminal Board to output the Preset Speed (see F018 for more information on
this parameter).
Direct Access Number — F290
Parameter Type — Numerical
Factory Default0.00
Changeable During Run — Yes
Minimum — Lower-Limit (F013)
Maximum — Upper-Limit (F012)
Units — Hz
Preset Speed 12
Program Preset Speeds
This parameter assigns an output frequency to binary number 1100 and is
identified as Preset Speed 12. The binary number is applied to S1S4 of the
Terminal Board to output the Preset Speed (see F018 for more information on
this parameter).
Direct Access Number — F291
Parameter Type — Numerical
Factory Default0.00
Changeable During Run — Yes
Minimum — Lower-Limit (F013)
Maximum — Upper-Limit (F012)
Units — Hz
Preset Speed 13
Program Preset Speeds
This parameter assigns an output frequency to binary number 1101 and is
identified as Preset Speed 13. The binary number is applied to S1S4 of the
Terminal Board to output the Preset Speed (see F018 for more information on
this parameter).
Direct Access Number — F292
Parameter Type — Numerical
Factory Default0.00
Changeable During Run — Yes
Minimum — Lower-Limit (F013)
Maximum — Upper-Limit (F012)
Units — Hz
Preset Speed 14
Program Preset Speeds
This parameter assigns an output frequency to binary number 1110 and is
identified as Preset Speed 14. The binary number is applied to S1S4 of the
Terminal Board to output the Preset Speed (see F018 for more information on
this parameter).
Direct Access Number — F293
Parameter Type — Numerical
Factory Default0.00
Changeable During Run — Yes
Minimum — Lower-Limit (F013)
Maximum — Upper-Limit (F012)
Units — Hz