Q9 ASD Installation and Operation Manual 151
Trace Cycle
No Path — Direct Access Only
This parameter sets the record time for the Trace Data events selected at
F742F745.
Settings:
0 — 4 ms
1 — 20 ms
2 — 100 ms
3 — 1 Second
4 — 10 Seconds
Direct Access Number — F741
Parameter Type — Selection List
Factory Default100 ms
Changeable During Run — Yes
Trace Data 1
No Path — Direct Access Only
This parameter is used to select the Trace Data 1 item to be read and stored from
the setup of parameters F740 and F741.
See F740 for more information on this parameter setting.
Direct Access Number — F742
Parameter Type — Selection List
Factory DefaultOutput Frequency
Changeable During Run — Yes
Trace Data 2
No Path — Direct Access Only
This parameter is used to select the Trace Data 2 item to be read and stored from
the setup of parameters F740 and F741.
See F740 for more information on this parameter setting.
Direct Access Number — F743
Parameter Type — Selection List
Factory DefaultFreq. Reference
Changeable During Run — Yes
Trace Data 3
No Path — Direct Access Only
This parameter is used to select the Trace Data 3 item to be read and stored from
the setup of parameters F740 and F741.
See F740 for more information on this parameter setting.
Direct Access Number — F744
Parameter Type — Selection List
Factory DefaultOutput Current
Changeable During Run — Yes
Trace Data 4
No Path — Direct Access Only4
This parameter is used to select the Trace Data 4 item to be read and stored from
the setup of parameters F740 and F741.
See F740 for more information on this parameter setting.
Direct Access Number — F745
Parameter Type — Selection List
Factory DefaultDC Voltage
Changeable During Run — Yes
kWH Memory Set
Program Special Controls
This parameter is used to set the disposition of the kWH meter reading at power
off.
Settings:
Save at Power Off
Clear at Power Off
Direct Access Number — F748
Parameter Type — Selection List
Factory DefaultSave at Power Off
Changeable During Run — No
F741 F748