154 Q9 ASD Installation and Operation Manual
Communications Time-Out Action (RS485 2- and 4-Wire)
Program Communication Settings
This parameter plays a role in the setup of the communications network by
determining the action to be taken in the event of a time-out (Time-Out Action).
The communications network includes other ASDs and Host/Control computers
that monitor the status of the ASD(s), transfers commands, and loads or modifies
the parameter settings of the drive.
Changes made to this parameter require that the power be cycled (off then on) for
the changes to take effect.
Settings:
0 — No Action/No Action
1 — Alarm/No Action
2 — Trip/No Action
3 — No Action/Alarm
4 — Alarm/Alarm
5 — Trip/Alarm
6 — No Action/Trip
7 — Alarm/Trip
8 — Trip/Trip
Direct Access Number — F804
Parameter Type — Selection List
Factory DefaultTrip/Trip
Changeable During Run — Yes
Send Wait Time (RS485 2-Wire)
Program Communication Settings
This parameter sets the RS485 response delay time.
Changes made to this parameter require that the power be cycled (off then on) for
the changes to take effect.
Direct Access Number — F805
Parameter Type — Numerical
Factory Default0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 2.00
Units — Seconds
F804 F805