Q9 ASD Installation and Operation Manual 153
Parity (RS485 2- and 4-Wire)
Program Communication Settings
This parameter plays a role in the setup of the communications network by
establishing the Parity setting of the communications link.
The communications network includes other ASDs and Host/Control computers
that monitor the status of the ASD(s), transfers commands, and loads or modifies
the parameter settings of the ASD.
Changes made to this parameter require that the power be cycled (off then on) for
the changes to take effect.
Settings:
0 — No Parity
1 — Even Parity
2 — Odd Parity
Direct Access Number — F801
Parameter Type — Selection List
Factory DefaultEven Parity
Changeable During Run — Yes
ASD Number
Program Communication Settings
This parameter plays a role in the setup of the communications network by
assigning an identification (ID) number to each ASD in the communications
network.
The communications network includes other ASDs and Host/Control computers
that monitor the status of the ASD(s), transfers commands, and loads or modifies
the parameter settings of the ASD.
Changes made to this parameter require that the power be cycled (off then on) for
the changes to take effect.
Direct Access Number — F802
Parameter Type — Numerical
Factory Default0
Changeable During Run — Yes
Minimum — 0
Maximum247
Communications Time Out Time (RS485 2- and 4-Wire)
Program Communication Settings
This parameter plays a role in the setup of the communications network by setting
the time that no activity may exist over the communications link before the link is
severed (Timed Out).
The communications network includes other ASDs and Host/Control computers
that monitor the status of the ASD(s), transfers commands, and loads or modifies
the parameter settings of the ASD.
Changes made to this parameter require that the power be cycled (off then on) for
the changes to take effect.
Direct Access Number — F803
Parameter Type — Numerical
Factory Default0 (Off)
Changeable During Run — Yes
Minimum — 0 (Off)
Maximum100
Units — Seconds