80 Q9 ASD Installation and Operation Manual
V/f 5-Point Setting Voltage 1
No Path — Direct Access Only
The V/f 5-Point Setting Voltage 1 establishes the output voltage level that is to
be associated with the frequency setting of F190 (V/f 5-Point Setting Frequency
1).
The F701 parameter setting will determine if the on-screen selection for this
parameter appears in the form of a Voltage (V) or as a Percentage (%) of the ASD
rating.
If using Voltage as a unit of measure and with no voltage correction (F307
Disabled), the limit of the on-screen display value for this parameter is 200 volts
for the 230-volt ASD and 400 volts for the 460-volt ASD.
The actual output voltage is scaled to the maximum EOI display values (e.g., a
100-volt EOI display corresponds to a 115-volt actual output for the 230-volt
ASD — ½ of the full display range).
If using % as a unit of measure and with no voltage correction (F307 Disabled),
the ASD output voltage will be the percentage setting times 230 for the 230-volt
unit (or % times 460 volts for the 460-volt unit).
See F190 for additional information on this setting.
Direct Access Number — F191
Parameter Type — Numerical
Factory Default0.0
Changeable During Run — No
Minimum — 0.0
Maximum — 100.0
Units — V or % (F701)
V/f 5-Point Setting Frequency 2
No Path — Direct Access Only
The V/f 5-Point Setting Frequency 2 sets the frequency to be associated with the
voltage setting of parameter F193 (V/f 5-Point Setting Voltage 2).
See F190 and F191 for additional information on this setting.
Direct Access Number — F192
Parameter Type — Numerical
Factory Default0.00
Changeable During Run — No
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
F191 F192