Q9 ASD Installation and Operation Manual 81
V/f 5-Point Setting Voltage 2
No Path — Direct Access Only
The V/f 5-Point Setting Voltage 2 establishes the output voltage level that is to
be associated with the frequency setting of F192 (V/f 5-Point Setting Frequency
2).
The F701 parameter setting will determine if the selection for this parameter
appears in the form of a Voltage (V) or as a Percentage (%) of the ASD rating.
The default setting is %.
See F190 and F191 for additional information on this setting.
Direct Access Number — F193
Parameter Type — Numerical
Factory Default0.0
Changeable During Run — No
Minimum — 0.0
Maximum — 100.0
Units — V or % (F701)
V/f 5-Point Setting Frequency 3
No Path — Direct Access Only
The V/f 5-Point Setting Frequency 3 sets the frequency to be associated with the
voltage setting of parameter F195 (V/f 5-Point Setting Voltage 3).
See F190 and F191 for additional information on this setting.
Direct Access Number — F194
Parameter Type — Numerical
Factory Default0.00
Changeable During Run — No
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
V/f 5-Point Setting Voltage 3
No Path — Direct Access Only
The V/f 5-Point Setting Voltage 3 establishes the output voltage level that is to
be associated with the frequency setting of F194 (V/f 5-Point Setting Frequency
3).
The F701 parameter setting will determine if the selection for this parameter
appears in the form of a Voltage (V) or as a Percentage (%) of the ASD rating.
The default setting is %.
See F190 and F191 for additional information on this setting.
Direct Access Number — F195
Parameter Type — Numerical
Factory Default0.0
Changeable During Run — No
Minimum — 0.0
Maximum — 100.0
Units — V or % (F701)
V/f 5-Point Setting Frequency 4
No Path — Direct Access Only
The V/f 5-Point Setting Frequency 4 sets the frequency to be associated with the
voltage setting of parameter F197 (V/f 5-Point Setting Voltage 4).
See F190 and F191 for additional information on this setting.
Direct Access Number — F196
Parameter Type — Numerical
Factory Default0.00
Changeable During Run — No
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
V/f 5-Point Setting Voltage 4
No Path — Direct Access Only
The V/f 5-Point Setting Voltage 4 establishes the output voltage level that is to
be associated with the frequency setting of F196 (V/f 5-Point Setting Frequency
4).
The F701 parameter setting will determine if the selection for this parameter
appears in the form of a Voltage (V) or as a Percentage (%) of the ASD rating.
The default setting is %.
See F190 and F191 for additional information on this setting.
Direct Access Number — F197
Parameter Type — Numerical
Factory Default0.0
Changeable During Run — No
Minimum — 0.0
Maximum — 100.0
Units — V or % (F701)
F193 F197