88 Q9 ASD Installation and Operation Manual
RR Reference 2
Program Frequency Settings
This parameter is used to set the gain and bias of the RR input terminal when the
RR terminal is used as the control input while operating in the Speed Control
mode or the Torque Control mode.
This parameter sets the RR input level that is associated with RR Frequency 2
when operating in the Speed control mode or is associated with the RR Torque
Reference 2 when operating in the Torque Control mode.
This value is entered as 0% to 100% of the RR input signal range.
See RR Reference 1 for more information on this setting when used for Speed
control.
See RR Torque Reference 1 (F214) for more information on this setting when
used for Torque Control.
Direct Access Number — F212
Parameter Type — Numerical
Factory Default100
Changeable During Run — Yes
Minimum — 0
Maximum100
Units — %
RR Frequency 2
Program Frequency Settings
This parameter is used to set the gain and bias of the RR input terminal when the
RR terminal is used as the control input while operating in the Speed Control
mode.
This parameter sets RR Frequency 2 and is the frequency that is associated with
the setting of RR Reference 2 when operating in the Speed Control mode.
See RR Reference 1 (F210) for more information on this setting.
Direct Access Number — F213
Parameter Type — Numerical
Factory Default60.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
F212 F213