Q9 ASD Installation and Operation Manual 89
RR Torque Reference 1
Program Frequency Settings
This parameter is used to set the gain and bias of the RR input terminal when the
RR terminal is used as the control input while operating in the Torque Control
mode.
RR Input Torque Control Setup
Perform the following setup to allow the system to receive Torque Control input
at the RR input terminal:
Program Utility Group Frequency Mode 1 RR.
Program Utility Group Command Mode Terminal Block.
Torque Control
Perform the following setup to allow the system to perform Torque Control from
the RR input terminal:
•Set RR Torque Reference 1 (F214).
•Set RR Reference 1 (F210) — the input analog signal level that corresponds
to the torque setting at RR Torque Reference 1.
•Set RR Torque Reference 2 (F215).
•Set RR Reference 2 (F212) — the input analog signal level that corresponds
to the frequency setting at RR Torque Reference 2.
Provide a Run command (F and/or R).
Torque Control is accomplished by establishing an associated V/f output pattern
for a given RR input level.
Once set, as the RR input voltage changes, the output torque of the ASD will vary
in accordance with the above settings.
This parameter sets RR Torque Reference 1 and is the output torque value that is
associated with the setting of RR Reference 1 when operating in the Torque
Control mode.
This value is entered as 0% to 250% of the rated torque.
Direct Access Number — F214
Parameter Type — Numerical
Factory Default0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.00
Units — %
Torque Settings
RR Torque Reference 2
Program Frequency Settings
This parameter is used to set the gain and bias of the RR input terminal when the
RR terminal is used as the control input while operating in the Torque Control
mode.
Torque Control is accomplished by establishing an associated V/f output pattern
for a given RR input level.
This parameter sets RR Torque Reference 2 and is the output torque value that is
associated with the setting of RR Reference 2 when operating in the Torque
Control mode.
This value is entered as 0% to 250% of the rated torque.
See RR Torque Reference 1 for more information on this setting.
Direct Access Number — F215
Parameter Type — Numerical
Factory Default100.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.00
Units — %
F214 F215