90 Q9 ASD Installation and Operation Manual
RX Reference 1
Program Frequency Settings
This parameter is used to set the gain and bias of the RX input terminal when the
RX terminal is used as the control input while operating in the Speed Control
mode or the Torque Control mode.
This parameter sets the RX input level that is associated with RX Frequency 1
when operating in the Speed Control mode or is associated with the RX Torque
Reference 1 when operating in the Torque Control mode.
RX Input Speed Control Setup
Perform the following setup to allow the system to receive Speed control input at
the RX input terminal:
• Program Utility Group Frequency Mode 1 RX.
• Program Utility Group Command Mode Terminal Block.
Speed Control
Perform the following setup to allow the system to perform Speed control from
the RX input terminal:
•Set RX Frequency 1 (F217).
•Set RX Reference 1 (F216) — the input analog signal level that corresponds
to the speed setting at RX Frequency 1.
•Set RX Frequency 2 (F219).
•Set RX Reference 2 (F218) — the input analog signal level that corresponds
to the speed setting at RX Frequency 2.
• Provide a Run command (F and/or R).
Once set, as the RX input voltage changes, the ASD output speed and/or torque
will vary in accordance with the above settings.
This parameter value is entered as -100% to +100% of the RX input signal range.
See parameter F474 and F475 for information on fine-tuning this terminal
response.
Direct Access Number — F216
Parameter Type — Numerical
Factory Default — 0
Changeable During Run — Yes
Minimum — -100
Maximum — +100
Units — %
Frequency Settings
RX Frequency 1
Program Frequency Settings
This parameter is used to set the gain and bias of the RX input terminal when the
RX terminal is used as the control input while operating in the Speed Control
mode.
This parameter sets RX Frequency 1 and is the frequency that is associated with
the setting of RX Reference 1 when operating in the Speed Control mode.
See RX Reference 1 (F216) for more information on this setting.
Direct Access Number — F217
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
F216 F217