2-2. Operation Characteristic Curve
<Cooling> <Heating>
2-3. Capacity Variation ratio According to Temperature.
<Cooling> <Heating>
0.00
1.00
2.00
3.00
4.00
5.00
6.00
7.00
8.00
9.00
0 102030405060708090100110120
Current (A)
Compressor Speed (RPS)
0
1
2
3
4
5
6
7
8
9
0 102030405060708090100110120
Current (A)
Compressor Speed (RPS)
Conditions
Indoor : DB 27
o
C/WB 19
o
C
Outdoor : DB 35
o
C/WB 24
o
C
Indoor Air Flow : High
Pipe Length : 5m
Voltage : 230V
Conditions
Indoor : DB 20
o
C/WB 15
o
C
Outdoor : DB 7
o
C/WB 6
o
C
Indoor Air Flow : High
Pipe Length : 5m
Voltage : 220V
RAS-07BAV-E
RAS-10BAV-E
RAS-07BAV-E
RAS-10BAV-E
RAS-13BAV-E
RAS-13BAV-E
FILE NO. SVM-16003
- 7 -
50
55
60
65
70
75
80
85
90
95
100
105
32 33 34 35 36 37 38 39 40 41 42 43 44 45 46
Cooling Capacity Ratio (%)
Outside Temperature (
o
C)
Capacity ratio 100% as below
07k = 2.0 kW
10k = 2.5 kW
13k = 3.1 kW
Conditions
Indoor : DB 27
o
C/WB 19
o
C
Outdoor : DB 35
o
C
Air Flow : High
Pip Length : 5m
Voltage : 230V
0
20
40
60
80
100
120
-15 -10 5 10
Heating Capacity Ratio (%)
-5 0
Outside Temperature (
o
C)
Capacity ratio 100% as below
07k = 2.5 kW
10k = 3.2 kW
13k = 3.6 kW
Conditions
Indoor : DB 20
o
C/WB 15
o
C
Outdoor :
DB7
o
C/WB6
o
C
Air Flow : High
Pip Length : 5m
Voltage : 230V