20
FILE NO. SVM-06037
5-6. RAS-07GKPX / RAS-07GAX
Note :
Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor)
Cooling
Standard 0.55 12.0 High 27/19 35/24
Overload 0.66 16.0 High 32/23 43/26
Low temperature 0.42 2.0 Low 21/15 21/15
50Hz
Fan speed
(indoor)
Ambient temp.
conditions DB/WB
(°C)
Indoor Outdoor
Standard
pressure P
(MPaG)
Surface temp. of heat
exchanger interchanging
pipe T1 (°C)
Indoor unit
Cross flow fan
Cooling
Cooling
Compressor
Heat exchanger
Propeller fan
Outdoor unit
PH108X1C-4DZDN2
Cooling
Mark( )means check points of Gas Leak.
O.D.:9.52mm O.D.:6.35mm
Cooling
Packed valve
(9.52)
Packed valve
(6.35)
0.39m
(Connecting pipe)
9.52
0.49m
(Connecting pipe)
6.35
T1
P
Refrigerant
R-22 : 0.63 kg.
Heat exchanger
Capillary tube
1.2x600S