56
FILE NO. SVM-06037
9-5-2. Power can not be turned on after replacing indoor P.C. board
<Checking Procedure>
Connect the AC
Power supply
Does the OPERATION
lamp blink?
Is it wired as shown
in Figure below?
Return the wiring of the
power relay is returned to
the normal procedure.
To the paragraph of
"No Power turns on".
YES
NO NO
YES
RAS-07GKHP-E, RAS-10GKHP-E
RAS-07GKP-E, RAS-10GKP-E
4
3
1
2
Black
White
Red
Blue
RY01
3
4
T02
CN31
Indoor Terminal Block
1
2
Black
White
RY01
3
4
CN31
Indoor Terminal Block
Green & yellow
L
N
Supply AC 220 ~ 240 V
50 / 60 Hz
Green & yellow
L
N
Supply AC 220 ~ 240 V
50 / 60 Hz
Brown
Blue
Brown
Blue