– 12 –
RAS-13SKH-ES/RAS-13SAH-ES
Heat exchanger
Indoor unit
Cross flow fan
Gas container connection (Reinstall etc.)
Heating
4-way valve
Heating
Cooling
Compressor
Condenser
Propeller fan
Outdoor unit
Capillary tube
ø1,5x500
Cooling
Cooling
Mark ( ) means check points of Gas Leak
O.D.:9,52mm O.D.:6,35mm
Cooling
Heating
Packed valve
(ø9,52)
Packed valve
(ø6,35)
0,49m
(Connecting pipe)
ø9,52
0,39m
(Connecting pipe)
ø6,35
(Note)
Maximum pipe length is 15m
Maximum pipe head is 6m
T1
P
Capillary tube
ø1,2x1200
Heating
Refrigerant
R-410A 0,80kg
PA160X2T-4FM
Muffler
Dryer
Standard pressure Surface temp. of heat
P exchanger interchanging Fan speed
50Hz (MPaG) pipe T1 (°C) (indoor)
RAS-13SKH-ES RAS-13SKH-ES
Standard 2,7 43,0 High
Heating High temperature*1 3,2 ~ 3,6 52,0 ~ 57,0 Low
Low temperature 2,0 30,0 High
Standard 0,9 11,0 High
Cooling High temperature 1,0 14,0 High
Low temperature 0,6 2,0 Low
Ambient temp.
conditions DB/WB
(°C)
Indoor Outdoor
20/– 7/6
27/– 21/15
20/– –10/–10
27/19 35/24
32/23 43/26
21/15 21/15
Note :
• Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
*
1 • During heating overload, the high temperature limit control operation is included.