18
FILE NO. SVM-03001
5-4.RAS-10UKP-ES2 / RAS-10UA-ES2
RAS-10UKP-AS2 / RAS-10UA-AS2
Note :
Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor)
Ambient temp.
conditions DB/WB
(°C)
Indoor Outdoor
Standard 0.95 11.0 High 27/19 35/24
Cooling Overload 1.15 15.0 High 32/23 43/26
Low temperature 0.85 5.0 Low 21/15 21/15
Fan speed
(indoor)
50Hz
Indoor unit
Cross flow fan
Cooling
Cooling
Compressor
Condenser
Propeller fan
Outdoor unit
PA108X1T-4FZ1
Cooling
Mark( )means check points of Gas Leak.
O.D.:9.52mm O.D.:6.35mm
Cooling
Packed valve
(9.52)
Packed valve
(6.35)
0.39m
(Connecting pipe)
9.52
0.49m
(Connecting pipe)
6.35
T1
P
Refrigerant
R410A : 0.65 kg.
Evaporator
Capillary tube
1.5x1100S
Standard
pressure
P
(MPaG)
Surface temp. of heat
exchanger interchanging
pipe
T1
(°C)