7-2. Operation Data
<Cooling>
<Heating>
NOTES :
1. Measure surface temperature of heat exchanger pipe around center of heat exchanger path U bent.
(Thermistor themometer)
2. Connecting piping condition : 5 m
Model name Standard Indoor Outdoor Compressor
RAS- pressure fan mode fan mode revolution
Indoor Outdoor P (MPa) T1 (°C) T2 (°C) (rps)
27/19 35/-
05BKVG-E
1.2 to 1.3
13 to 15
43 to 45
High
High
36
07BKVG-E
1.1 to 1.3
11 to 13
47 to 49
High High
52
10BKVG-E
1.1 to 1.3 11 to 13 59 to 51
High High
52
condition(°C)
Tempeature Heat exchanger
pipe temp.
Model name Standard Indoor Outdoor Compressor
RAS- pressure fan mode fan mode revolution
Indoor Outdoor P (MPa) T1 (°C) T2 (°C) (rps)
20/- 7/6
2.1 to 2.2 34 to 36
1 to 2
High High
51
2.1 to 2.4 35 to 40
0 to 1 High High
65
2.4 to 2.6 40 to 42
0 to 1 High High
68
condition(°C)
Tempeature Heat exchanger
pipe temp.
05BKVG-E
07BKVG-E
10BKVG-E
13BKVG-E
1.0 to 1.1 9 to 10 51 to 52
High High
78
16BKVG-E
1.0 to 1.1 9 to 10 47 to 58
High High
86
2.6 to 2.7 43 to 44 0 to 1
High High
73
2.8 to 2.9 45 to 47 1 to 2
High High
84
13BKVG-E
16BKVG-E