4-1. Indoor Unit
No. Parts name Type Specifications
1 Fan motor (for indoor) AFP-220-50-4A Output (Rated) 50W, 220-240V
2 Thermo sensor (TA-sensor) ——— 10k at 25°C
3 DC-DC transformer (T01) SWT-47 DC 390V, Secondary DC 12V, 7V
4 Microcomputer TMP87CM40AN
5
Heat exchanger sensor
——— 10k at 25°C
(TC-sensor)
6 Line filter (L01) SS11V-R07190 19mH, AC0.7A
7 Diode (DB01) D3SBA60 4A, 600V
8 Capacitor (C02) KMH400VSSN47M22S 47µF, 400V
9 Fuse (F01) TSCR T6.3A, 250V
10 Varistor (R21, R22) TND15G561K 560V
11 Resistor (R01) RF-2TK5R6 5.6, 2W
12 Louver motor MP35EA12
Output (Rated) 2W, 6poles, 4phase,
DC 12V
4-2. Outdoor Unit (RAS-18NAH-E)
No. Parts name Type Specifications
Output (Rated) 1500 W, 2 poles, 1 phase, 220 – 240 V, 50 Hz
1 Compressor PH340X3C-4KT1 Winding resistance () C-R C-S
(at 20°C) 1.46 2.47
Output (Rated) 42 W, 4 poles, 1 phase, 220 – 240 V, 50 Hz
2 Fan motor (for outdoor) FG-240-42A-1 Winding resistance () Red-Black White-Black
(at 20°C) 128 126
3
Running capacitor
451305L AC 450 V, 3.0µF
(for fan motor)
4
Running capacitor
RS44B506U0218S AC 440 V, 50µF
(for compressor)
5
Solenoid coil
VHV (STF) AC 220 – 240 V
(for 4-way valve)
6 Thermo sensor TE / TD 10 k at 25°C / 50 k at 25°C
7 Magnetic contactor
CLK-26J
220 240 V, 50 Hz
8 Transformer TT-05 220 – 240 V
9 Microcontroller TMP47C840N
10 Varistor (R73, R74, R86) 15G471K 470 V
11 Fuse (F01) MT3 T6.3 A, 250 V