– 3 –
FILE NO. SVM-06006
1. SPECIFICATIONS
1-1
RAS-B18UFPX5/18N2AX
Cooling Heating Cooling
Capacity kW 220V 240V 220V 240V 220V 240V
5.00 5.70 5.80 5.20 5.25
Phase 1∅
Power source V 220 – 240
Hz 50
Power consumption W 2000 2130 1830 2000 2000 2120
Power factor % 95 87 93 84 96 91
Running current
Indoor A 0.40 0.40 0.40 0.40 0.40 0.40
Outdoor A 9.20 9.85 8.50 9.50 9.05 9.30
Starting current A
Moisture removal lit/h 2.0
Noise
Indoor (H/M/L) dB 43/41/39/37/36
Outdoor dB 52 53 53 54 51 52
Refrigerant
Name of refrigerant R-22
Rated amount kg 1.53 1.0
Refrigerant control Capillary tube
Gas side size mm ∅12.70
Connection type Flare connection
Liquid side size mm ∅6.35
Interconnection Connection type Flare connection
pipe Maximum length m 15*
1
(One way) 20*
2
Maximum height m
8
difference
INDOOR UNIT RAS-18UFHP-E5
RAS-18UFP-E5
RAS-B18UFPX5
Width mm 1093
Dimensions Height mm 633
Depth mm 208
Net weight kg 23
Evaporator type Finned tube
Indoor fan type Multi blade fan
High fan m
3
/h 800 830 800
Air volume Medium fan m
3
/h 680 700 680
Low fan m
3
/h 580 650 580
Fan motor output W 50
Air filter Washable -filter
OUTDOOR UNIT
RAS-18N2AX
Width mm
Dimensions Height mm
Depth mm
Net weight kg 43 41
Condenser type Finned tube
Outdoor fan type Propeller fan
Airflow volume m
3
/h 2350 2450 2350 2450 2350 2450
Fan motor output W 65 42
Compressor
Model PH340X3C-4KT1
Output W
Safety device IOL, Td Sensor IOL
Louver type Automatic louver
Usable outdoor temperature range °C 15 ~ 43 –10 ~ 24 21 ~ 43
MODEL
ITEM
1500
1500
45
42
Note *1 Chargeless pipe
*2 Maximum pipe
780
550
290
RAS-18UFP-E5/18NA-E
RAS-18UFHP-E5/18NAH-E
RAS-18NA-E
RAS-18NAH-E