Loading...
– 3 –
FILE NO. SVM-04008
MODEL
RAS-24UKHP-E3 RAS-24UKP-E3 RAS-24UKPX3 RAS-24UKP-AR3 RAS-24UKPX3-T
RAS-24UAH-E3
RAS-24UAX3
RAS-24UA-AR3 RAS-24UAX3-T
ITEM Cooling Heating Cooling Cooling Cooling Cooling
Capacity kW
220 V 240 V 220 V 240 V
220 V 240 V 220 V 240 V 220 V 240 V 220 V
6.30 6.30 6.80 6.90 6.40 6.45 6.40 6.45 6.40 6.45 6.40
Phase 1
Power source V 220 – 240 220
Hz 50
Power consumption W
2430 2510 2390 2490
2350 2440 2350 2440 2350 2440 2350
Power factor % 96 92 94 90 99 90 99 90 96 91 99
220 V 240 V 220 V 240 V
220 V 240 V 220 V 240 V 220 V 240 V 220 V
Running current A 0.3/ 0.3/ 0.3/ 0.3/
0.3/10.5 0.3/10.8 0.3/10.50 0.3/10.8 0.3/10.9 0.3/10.8 0.3/10.50
Indoor/Outdoor 11.2 11.1 11.2
11.28
Starting current A 60 67 67 67 48
Moisture removal lit/h 2.5 2.7
Noise
Indoor (H/M/L) dB 45/41/37
Outdoor (220 – 240 V) dB 56-57 57-58 56-57 56
Refrigerant
Name of refrigerant R22
Rated amount kg
Refrigerant control Capillary tube
Gas side size
mm
15.88
Connection type Flare connection
Liquid side size
mm
6.35
Interconnection Connection type Flare connection
pipe Maximum length
m
15*
1
(One way) 25*
2
Maximum height
m10
difference
INDOOR UNIT RAS-24UKHP-E3 RAS-24UKP-E3 RAS-24UKPX3 RAS-24UKP-AR3 RAS-24UKPX3-T
Height mm 298
Dimensions Width mm 998
Depth mm 208
Net weight kg 12
Evaporator type Finned tube
Indoor fan type Cross flow fan
High fan m
3
/h 950
Air volume Medium fan m
3
/h 750 800 750
Low fan m
3
/h 600 650 600
Fan motor output W 30
Air filter Honeycomb woven filter with PP frame
OUTDOOR UNIT RAS-24UAH-E3 RAS-24UA-E3 RAS-24UAX3 RAS-24UA-AR3 RAS-24UAX3-T
Height mm 690
Dimensions Width mm 880
Depth mm 310
Net weight kg 64
58
Condenser type Finned tube
Outdoor fan type Propeller fan
Airflow volume m
3
/h 3380 3560 3380 3560 3380 3560 3380 3560 3380
Fan motor output W 65
Compressor
Model PH310X3-4MM 2JS386D5BB02
Output W 2200 1800
Safety device IOL, Td Sensor IOL
Louver type Automatic louver
Usable outdoor temperature range °C 15 ~ 43 –10 ~ 24 15 ~ 43 15 ~ 43 15 ~ 52 15 ~ 43
1. SPECIFICATIONS
RAS-24UA-E3
1.63
1.80 1.80 1.63 1.80