EasyManua.ls Logo

Toshiba RAS-B24B2KVG-E - Refrigerant Piping Connection; Flaring Process; Tightening Flare Connections

Toshiba RAS-B24B2KVG-E
13 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6
Flare nut
Half union
Externally
threaded side
Internally
threaded side
Use a wrench to secure. Use a torque wrench to tighten.
CAUTION
Align the centers of the connecting pipes and tighten the are nut as far as
possible with your ngers. Then tighten the nut with a spanner and torque
wrench as shown in the gure.
Tightening connection
Do not apply excess torque. Otherwise, the nut may crack depending on
the conditions.
(Unit : N·m)
Outer dia. of copper pipe Tightening torque
Ø6.35 mm 14 to 18 (1.4 to 1.8 kgf·m)
Ø9.52 mm 30 to 42 (3.0 to 4.2 kgf·m)
Ø12.70 mm 50 to 62 (5.0 to 6.2 kgf·m)
Flare at
indoor unit side
Flare at
outdoor unit side
Tightening torque of are pipe connections
The operating pressure of R32 is
higher than that of R22 (approx.
1.6 times). It is therefore necessary
to rmly tighten the are pipe
connecting sections (which connect
the indoor and outdoor units) up to the
speci ed tightening torque. Incorrect
connections may cause not only a
gas leakage, but also damage to the
refrigeration cycle.
Refrigerant Piping Connection
Flaring
1. Cut the pipe with a pipe cutter.
90
Obliquity Roughness Warp
2. Insert a are nut into the pipe and are the pipe.
Projection margin in aring : A (Unit : mm)
RIDGID (clutch type)
Outer dia.
of copper pipe
R32 tool used
Conventional tool
used
Ø6.35 0 to 0.5 1.0 to 1.5
Ø9.52 0 to 0.5 1.0 to 1.5
Ø12.70 0 to 0.5 1.0 to 1.5
Pipes thickness 0.8 mm or more
IMPERIAL (wing nut type)
Outer dia. of copper pipe R32
Ø6.35 1.5 to 2.0
Ø9.52 1.5 to 2.0
Ø12.70 2.0 to 2.5
Pipes thickness 0.8 mm or more
A
Die
Pipe
Do not scratch the inner surface of the ared part when removing burrs.
• Flare processing under the condition of scratches on the inner surface
of fare processing part will cause refrigerant gas leak.
CAUTION