(˚C)
F4F5
F5
47
42
No.
6
Item
Air speed
selection
(Continued):
Outline of specifications
3) In heating operation, the mode changes to [UL] if thermostat
is turned off.
4) If Ta ≥ 25°C when heating operation has started and when
defrost operation has been cleared, the air conditioner
operates with (H) mode or higher mode for 1 minute after Tc
entered in E zone of cool air discharge preventive control
(Item 7).
5) In automatic cooling/heating operation, the revolution
frequency of (HH) is set larger than that in the standard
cooling/heating operation.
However the revolution
frequency is restricted in the
automatic heating operation as
shown in the following figure.
6) Self-clean operation
When performing self-clean operation after stopping the
cooling operation, the mode becomes [UL].
CODE No.
[5d]
SW501 (1)/(2)
Tap
F1
F2
F3
F4
F5
F6
F7
F8
F9
FA
FB
FC
FD
Standard Type 1 Type 3
013
OFF/OFF ON/OFF OFF/ON
HEAT COOL HEAT COOL HEAT COOL
HH HH
HH HH
H+ H+, H H+, H
H+
HH H
HH H L+ L+
H+ H+ L L
HL+
HL+L
L+ L
L+ L
L
Remarks
Selection of high
ceiling type
CODE No.:
[5d] or selection of
high ceiling on P.C.
board SW501
However only when
Selt-clean is not 
factory default.
Tcj:
Indoor heat exchanger
sensor temperature
the high ceiling
selection is set to
[Standard]
[Self-clean
] is
displayed.
Self-clean is not
factory default.
Tc
Tcj
UL UL UL UL UL UL
Tap
HM56 HM80  HM110 HM140 
Revolution speed (rpm)
F1 1000 1000 1140 1140
F2 880 910 1020 1080
F3 850 910 950 1000
F4 830 910 930 1000
F5 820 910 910 990
F6 790 910 910 990
F7 710
740
730 810
F8 700
730
720 790
F9 690
730
710 780
FA 590 610 630 710
FB
560
560 580 660
FC 550 550 570 640
FD 350 350 350 350
HM40 
1000
830
800
790
780
780
690
670
660
590
560
550
350
HM160 
1140
1080
1020
1000
990
990
860
840
830
740
680
670
350
HM90 
1000
900
830
820
820
820
740
730
730
640
590
5
80
350