EasyManua.ls Logo

Toshiba RAV-HM401CTP Series - Manual Address Setup from Remote Controller; Manual Address Setup Procedure Overview

Toshiba RAV-HM401CTP Series
118 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10-3. Address Setup (Manual Setting from Remote Controller)
(Example of 2-lines wiring)
(Solid line: Wiring, Broken line: Refrigerant pipe)
For the above example, perform setting by
connecting singly the wired remote controller
without remote controller inter-unit wire.
Outdoor
Indoor
AB
AB
123
Indoor
AB
123
Indoor
AB
123
Indoor
AB
123
123
Outdoor
123
Remote controller
Line address 1
Indoor unit address 1
Group address 1
1
2
2
2
1
2
2
2
2
In case that addresses of the indoor units will be
determined prior to piping work after wiring work
Set an indoor unit per a remote controller.
Turn on power supply.
Indoor unit
address
Group
address
CODE No.
(DN)
Item
13
14
Description
0001: No.1 to 0128: No.128 … TU2C-Link
0001: No.1 to 0030: No.30 … TCC-Link
12 Line address
0001: No.1 to 0128: No.128 … TU2C-Link
0001: No.1 to 0030: No.30 … TCC-Link
0000: Individual
0001: Header unit
0002: Follower unit
<RBC-ASCU1
>
1 Push and hold the [menu + ] buttons at same time for more than 10 seconds.
2 Push the [OFF timer] button to confirm the selected indoor unit.
<Line address>
3 Push the [menu] button until the CODE No. flashes. And using the [ or ] buttons,
specify the CODE No.12.
4 Push the [menu] button until the SET DATA flashes. And using the [ or ] buttons, set
a system address.
5 Push the [OFF timer] button to confirm the SET DATA.
2
3,4
3,4
3,4
6
2,5
- 97 -