Toshiba RAV-HM401CTP Series - Setup at Local Site and Others; Indoor Unit Setup Procedures; Test Run Setup via Remote Controller

Toshiba RAV-HM401CTP Series
118 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1 Push and hold OFF timer button and [ ] setting button simultaneously for 10 seconds or
more. [TEST] is displayed on the display part and the test run is permitted.
2 Push ON/OFF button.
3 Push menu button to select the operation mode. Select [ Cool] or [ Heat] with [ ]
[
] setting button.
Do not run the air conditioner in a mode other than [Cool] or [Heat].
The temperature setting function does not work during test run.
The check code is displayed as usual.
4 After the test run, push OFF timer button to stop a test run.
([TEST] disappears on the display and the air conditioner enters the normal stop mode.)
9. SETUP AT LOCAL SITE AND OTHERS
9-1. Indoor Unit
9-1-1. Test Run Setup on Remote Controller
<RBC-ASCU1
>
Be sure to stop the air conditioner before making settings.
(Change the setup while the air conditioner is not working.)
4
31 2
3
- 75 -