(Repeats)
No.
12
Item
Louver control
Outline of specifications
1) Louver position setup
When the louver position is changed, the position moves
necessarily to downward discharge position once to return to
the set position.
The louver position can be set up in the following operation range.
In cooling/dry operation In heating/fan operation
In group twin/triple operation, the louver positions can be set
up collectively or individually.
2) Swing setup
[SWING] is displayed and the following display is repeated.
In all operations
In group twin/triple operation, the louver positions can be
set up collectively or individually.
3) When the unit stopped or the alarm was output, the louver is
automatically set to full closed position.
4) When PRE-HEAT
(Heating ready) is displayed
(Heating operation started or defrost operation is performed),
heating thermo is off (or self-cleaning) is performed, the louver is
automatically set to horizontal discharge position.
Remarks
Alarm :
A check code is
displayed on the
remote controller,
and the indoor unit
stops.
(Excluding [F08]
and [L31])
- 34 -