Toshiba RAV-HM401CTP Series - P.C. Board Replacement - Setting Data Continued; Required CODE Numbers for Setting Data

Toshiba RAV-HM401CTP Series
118 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1. The Code No. for the Indoor unit type and Indoor unit capacity are
required to set the rotation number setting of the fan.
2. If the system/indoor/group addresses are different from those
before replacement, the auto-address setting mode starts and the
manual resetting may be required again.
(when the multiple units group operation including twin system.)
Step3 After writing down all setting data, push [ON/OFF] button to return to the normal stop status.
(It takes approx. 1 min until the remote controller operation is available again.)
CODE No. required at least
DN
10
11
12
13
14
E0
Contents
Type
Indoor unit capacity
Line address
Indoor unit address
Group address
Destination
- 70 -